HON’s Wiki # APC PDUs
Home / Power
Contents
AP7850 Metered PDU
Network Configuration Methods
The TCP/IP settings for the PDU may be configured using the following methods:
- The APC Device IP Configuration Wizard: A Windows program.
- DHCP/BOOTP: Requires special configuration of the DHCPv4 server.
- Local computer: Using some special RJ-11 serial cable.
- Remote computer: Using some ARP and ping hack and then telnet.
Remote Computer
- Connect the PDU and the computer to the same VLAN.
- Check the status LED. It should be blinking green and/or orange to indicate that it has an invalid TCP/IP configuration and/or is trying to request BOOTP configuration, respectively. If it’s solid green it means it’s already configured.
- Find the MAC address of the PDU. Either read from the label on the device, or watch the DHCP server log for the VLAN for (failed) requests.
- Add a static ARP entry to the PC to bind the PDU’s MAC address to the desired IPv4 address.
- Windows:
arp -s 10.10.10.10 00-c0-b7-63-9f-67
(example)
- Linux:
arp -s 10.10.10.10 00:c0:b7:63:9f:67
(example)
- Ping the IP address with a packet size of 113 bytes to set the address on the PDU.
- Windows:
ping 10.10.10.10 -l 113
- Linux:
ping 10.10.10.10 -s 113
- Telnet into the device:
telnet 10.10.10.10
- Log in using username and password
apc
.
- Navigate to the network settings to configure it correctly.
hon.one
| HON95/wiki